Bus-Bar
Protection Schemes.
•
500, 400, 275, 220 and 132 KV. Bus-Bar Protection Scheme.
- Differential Protection For each section of bus-bar.
- SF6 Pressure low Trip.
•
66 and 33 KV. Bus-Bar Protection Scheme.
-
Differential Protection For each
section of bus-bar or Arc protection or Micro switch protection.
-
SF6 Pressure low Trip.
•
22 and 11 KV BUS-Bar
Protection Scheme.
- Arc
protection or Micro switches protection.
•
500, 400, 275, and 220 KV BB section & BB couplers protection
scheme.
- I.D.M.T Non Directional O/C & E/F Relay.
- C.B Fail to Trip.
- SF6 Pressure Trip.
- Inter Trip (through pilot cable).
•
132 KV BB section & BB couplers protection scheme.
- I.D.M.T Non Directional O/C & E/F Relay.
- C.B Fail to Trip.
•
33 KV BB section & BB couplers protection scheme.
- I.D.M.T Non Directional O/C & E/F Relay.
•
11 KV BB section & BB couplers protection scheme.
- I.D.M.T Non Directional O/C & E/F Relay.
Shunt Reactor Protection Scheme.
275 &132 KV. Shunt Reactor Protection
Scheme.
•
I.D.M.T Non Direction O/C &
E/F relay.
•
Inter Trip (through pilot
cable – SHR connected through cable C.B. “for 132 kV only”).
•
Buchhols Trip.
•
Oil Temperature Trip.
•
Winding Temperature Trip.
•
Cable oil pressure Low Trip.
(For cable tails)
•
SF6 pressure Low Trip.
•
C.B Fail to trip. (For 132
KV. C.B only).
33
KV. Shunt Reactor Protection Scheme for both connected
to 33 KV Bus-Bar or to tertiary of 300 MVA Transformer.
•
I.D.M.T Non Direction O/C & E/F relay.
•
Buchhols Trip.
•
Oil
Temperature Trip.
•
Winding Temperature Trip.
|