Some types of
power transformers
•
300 MVA. 3 Winding Power
Transformer
275 KV / 132 KV / 33 KV. (Y.Y.Δ).
•
75 MVA. & 45 MVA. 2 Winding
Power Transformer 1
32 KV / 33 KV.
•
30 MVA 2 Winding Power
Transformer
132 KV / 11 KV.
•
20 MVA & 15 MVA 2 Winding
Power Transformer
33 KV / 11 KV.
Drawing
: single Line diagram for
protection scheme
Click Here
300 MVA
3 Winding Power Transformer
Protection Scheme.
•
Main
(A&B) Protection:
1.
Differential Protection.
2.
Restricted Earth Fault
Protection. (both at 275 kv and 132 kv)
side neutral of the star winding.
•
BackupProtection:
-
C.B Fail to trip.
-
I.D.M.T Non Direction O/C &
E/F relay on 300 KV side
-
I.D.M.T Direction O/C & E/F
relay on 132 KV side
-
Inter Trip (through pilot
cable).
-
Buchhols Trip.
-
Tap Changer Buchhols Trip.
-
Oil Temperature Trip.
-
Winding Temperature Trip.
-
Cable oil pressure Low Trip.
(for cable tails )
-
SF6 pressure Low Trip.
75, 45 And 30 MVA- 2 Winding Power Transformer
Protection Scheme.
•
Main
(A) Protection:
1.
Differential Protection.
2.
Restricted Earth Fault
Protection.
(At the neutral of the LV. Winding).
•
Backup
Protection:
-
Stand-By Earth Fault relay at
the neutral of LV. Winding.
-
C.B Fail to trip. (For 132
KV. C.B only)
-
I.D.M.T Non Direction O/C &
E/F relay on 132 KV side
-
Inter Trip (through pilot
cable).
-
Buchhols Trip.
-
Tap Changer Buchhols Trip.
-
Winding Temperature Trip.
-
Cable oil pressure Low Trip.
(For cable tails)
20 & 15 MVA- 33 / 11 KV, 2 Winding Power
Transformer
Protection Scheme.
•
Main
(A) Protection:
1.
Differential Protection.
2.
Restricted
Earth Fault Protection.
(At the neutral of the LV. Winding).
•
Backup
Protection:
-
Stand-By Earth Fault relay at
the neutral of LV. Winding.
-
I.D.M.T Non Direction O/C &
E/F relay on 33 KV side
-
Inter Trip (through pilot
cable).
-
Buchhols Trip.
|