|
Important
considerations when design protection system.
-
Types
of fault and abnormal Conditions to be protected against
-
Quantities available for measurement
-
Types
of protection available
-
Speed
-
Fault
position discrimination
-
Dependability / reliability
-
Security / stability
-
Overlap of protections
-
Phase
discrimination / selectivity
-
CT’s
and VT’s ratio required
-
Auxiliary supplies
-
Back-up protection
-
Cost
-
Duplication of protection
|
|
|
Types of
protection
A - Fuses
For LV Systems, Distribution Feeders and Transformers, VT’s,
Auxiliary Supplies
B - Over current and earth fault
Widely used in All Power Systems
-
Non-Directional
-
Directional.
|
|
|
C - DIFFERENTIAL
For feeders, Bus-bars, Transformers, Generators etc
-
High
Impedance
-
Low
Impedance
-
Restricted E/F
-
Biased
-
Pilot
Wire
|
|
D - Distance
For transmission and sub-transmission lines and
distribution feeders, also used as back-up protection for
transformers and generators without signaling with signaling to
provide unit protection e.g.:
-
Time-stepped distance protection
-
Permissive underreach protection (PUP)
-
Permissive overreach protection (POP)
-
Unblocking overreach protection (UOP)
-
Blocking
overreach protection (BOP)
-
Power
swing blocking
-
Phase
comparison for transmission lines
-
Directional comparison for transmission lines
E - Miscellaneous:
-
Under
and over voltage
-
Under
and over frequency
-
A
special relay for generators, transformers, motors etc.
-
Control relays: auto-reclose, tap change control, etc.
-
tripping and auxiliary relays
Speed
Fast operation:
minimizes damage and danger
Very fast operation:
minimizes system instability discrimination and security can
be costly to achieve.
Examples:
-
differential protection
-
differential protection with digital signaling
-
distance protection with signaling
-
directional comparison with signaling
Fault position discrimination
Power system divided into protected zones must
isolate only the faulty equipment or section
Dependability / reliability
Protection must operate when required to Failure to
operate can be extremely damaging and disruptive Faults are rare.
Protection must operate even after years of inactivity Improved by
use of:
-
Back-up Protection and
-
duplicate Protection
Security / Stability
Protection must not operate when not required to e.g.
due to:
-
Load
Switching
-
Faults
on other parts of the system
-
Recoverable Power Swings
Overlap of protections
-
No
blind spots
-
Where
possible use overlapping CTs
Phase discrimination / selectivity
Correct indication of phases involved in the fault
Important for Single Phase Tripping and auto-Reclosing applications
Current and voltage transformers
These are an essential part of the Protection Scheme.
They must be suitably specified to meet the requirements of the
protective relays.
1A and 5A secondary current ratings,
Saturation of current transformers during heavy fault conditions
should not exceed the limits laid down by the relay manufacturer.
Current transformers for fast operating protections
must allow for any offset in the current waveform. Output rating
under fault conditions must allow for maximum transient offset. This
is a function of the system X/R ratio.
Current Transformer Standards/Classes:
British Standards: 10P, 5P, X
IEC: 10P, SP, TPX, TPY, TPZ
American: C, T.
Location of CTs should, if possible, provide for
overlap of protections. Correct connection of CTs to the protection
is important. In particular for directional, distance, phase
comparison and differential protections. VT’s may be Electromagnetic
or Capacitor types. Busbar VT’s: Special consideration needed when
used for Line Protection.
Auxiliary supplies
Required for:
-
Tripping circuit breakers
-
Closing circuit breakers
-
Protection and trip relays
-
AC. auxiliary supplies are only used on LV and MV systems.
-
DC. auxiliary supplies are more secure than ac supplies.
-
Separately fused supplies used for each protection.
-
Duplicate batteries are occasionally provided for extra
security.
-
Modern protection relays need a continuous auxiliary supply.
-
During operation, they draw a large current which increases
due to operation of output elements.
Relays are given a rated auxiliary voltage and an
operative auxiliary voltage range.
the rated value is marked on the relay. Refer to
relay documentation for details of operative range. it is important
to make sure that the range of voltages which can appear at the
relay auxiliary supply terminals is within the operative range.
IEC recommended values (IEC 255-6):
Rated battery voltages:
12, 24, 48, 60, 11 0, 125, 220, 250, 440
Preferred operative range of relays:
80 to 10% of voltage rated
AC. component ripple in the dc supply:
<10% of voltage rated
COST
The cost of protection is equivalent to insurance
policy against damage to plant, and loss of supply and customer
goodwill.
Acceptable cost is based on a balance of economics
and technical factors. Cost of protection should be balanced against
the cost of potential hazards there is an economic limit on what can
be spent.
Minimum cost:
Must ensure that all faulty equipment is isolated by
protection
Other factors:
-
Speed
-
Security/Stability
-
Sensitivity:
Degree of risk in allowing a low level fault to develop
into a more severe fault
-
Reliability
Total cost should take
account of:
-
Relays, schemes and associated panels and panel wiring
-
Setting studies
-
Commissioning
-
CT’s
and VT’s
-
Maintenance and repairs to relays
-
Damage
repair if protection fails to operate
-
Lost
revenue if protection operates unnecessarily
Distribution systems
-
Large
number of switching and distribution points, transformers and
feeders.
-
Economics often overrides technical issues
-
Protection may be the minimum consistent with - statutory safety
regulations
-
Speed
less important than on transmission systems
-
Back-up protection can be simple and is often inherent in the
main protection.
-
Although important, the consequences of maloperation or failure
to operate are less
serious than for transmission systems.
Transmission systems
-
Emphasis is on technical considerations rather than economics
-
Economics cannot be ignored but is of secondary importance
compared with the need for highly reliable, fully
discriminative high speed protection
-
Higher
protection costs justifiable by high capital cost of power
system elements protected.
-
Risk
of security of supply should be reduced to the lowest practical
levels
-
High
speed protection requires unit protection
-
Duplicate protections used to improve reliability
-
Single
phase tripping and auto-reclose may be required to maintain
system stability
|